I just looked at a spec sheet for a 230V single-phase 12k BTU mini-split and the minimum circuit ampacity was 3A for the air handler and 12A for the condenser, add those together for 15A, divide by .8 is 18.75A, next size up is 20A. Minimum circuit ampacity is a formula that is (roughly) the sum of the full load amps of the motor(s) inside the piece of equipment times 1.25 to determine the conductor size required to power the equipment.
So the condensing unit likely draws ~9.5-10A max and the air handler around ~2.4A, and both will have variable speed motors that would probably only need about half of that to remove 12k BTU of heat, so ~5-6A or thereabouts should do it, which is around 1/3rd of the 16A server, or a COP of 3.
In this case, 12A is the maximum continuous load allowed on a 15A breaker. The unit itself probably uses between 900-1000w (7.5A to 8.3A), the spec sheet might say 12A to encourage a dedicated circuit for the A/C unit which then gets added to Amazon’s specs on their website.
The amazon page specifically said 1354 watts, but I think that's actually for the 14300BTU model. 12000BTU is 9.72 amps.
Anyway, doesn't this make my actual argument stronger? These units fit even better into a normal circuit than I thought, and make the mini-split look even worse in comparison.