The wye ground is beneficial even if there are no three phase loads, because the line-ground voltage is 1/sqrt(3) and you can use cheaper switchgear.
The 3-phase alternative to a wye ground is a corner ground (grounding a live phase of a delta secondary), which isn't done in modern installations because ground faults are full line-line voltage and you need more expensive switchgear.
Line-line faults are always interrupted by two breakers on a wye grounded 3 phase system. But with a corner ground, one breaker potentially has to break the full line voltage for a line-ground fault (you can't fuse the grounded phase).